Cover Off Enquire

Compare

Polyolefin or silicone line cover? An honest comparison

A 400 sq.mm bare overhead conductor is 28 mm across the strands, and three published cover constructions will go over it.

The fork is the fitting tool, not the dielectric

Both families are non-tracking, both are tested to ASTM D2303 with no tracking, erosion or flame failure up to 3.25 kV for 20 minutes, and both go onto metal that is already strung up in the air. On dielectric strength alone there is almost nothing to choose between them: 20 kV/mm minimum (ASTM D149) for the cross-linked polyolefin GOC, against >210 kV/cm (ASTM D149) for the self-locking silicone GSOC. Those two figures are the same order of magnitude — 210 kV/cm is 21 kV/mm — printed in different units because the two datasheets were drawn up at different times.

What genuinely separates them is how the cover gets onto the conductor. GOC is a wrap-around cover installed with the Split Insulation Tube Tool, and the manufacturer's description is specific that the tool stays in one location for the fit — the conductor is fed through it. GSOC needs no special tool, and its sheet records that it is installable without difficulty at 0 °C. If your crew is on a live-line pole platform partway along a span, that single row decides the job before any electrical figure is read.

The third construction, interlocking silicone GSIOC, sits between them on paper and below both on voltage: it field-installs over bare conductors for phase-to-phase and phase-to-earth insulation up to 33 kV. It is the option to look at when you want silicone's handling but the run is short and the class is medium voltage.

The seven rows that actually decide it

Three constructions the same manufacturer publishes for the same bare conductor. There is no cost row here and there will not be one: no price, lead time or minimum quantity appears in any of the published sheets, and a made-up figure in a comparison table is worse than a missing one.

DecisionPolyolefin GOC (Insulcover)Silicone GSOC (self-locking)Silicone GSIOC (interlocking)
Fitting toolSplit Insulation Tube Tool, held at one stationary locationNone. Self-locking, installable without difficulty at 0 °CNone. Interlocking, field-installed on the conductor
Published voltage ceiling66 kV on the Insulation Enhancement Products sheet; 400 kV on the Insulcover product page765 kV (GSOC-EH). 12 kV for GSOC-M, 36 kV for GSOC-H and GSOC-H333 kV
Wall thicknessNot published in the GOC selection chart2.0 mm (M), 2.7 mm (H), 3.0 mm (H3), 5.0 mm (EH)Not published
Roll length30 metres per roll, GOC 1 to GOC 415 metres per roll, every class and sizeNot published
Hardness40 ± 5 Shore D (ASTM D2240)Not published on the GSOC sheet65 ± 5 Shore A (ASTM D2240)
Tensile strength9 N/mm² min. (ASTM D638)7 N/mm² min. (ASTM D638)4 N/mm² min. (ASTM D638)
Temperature−45 to +105 °C continuous (IEC 216); no cracking at −40 °C for 4 hrs (ASTM D2671)Air ageing 150 °C for 168 hrs (ASTM D2671); installs at 0 °CNo cracking at −20 °C for 4 hrs (ASTM D2671); thermal ageing 150 °C for 168 hrs (ASTM D2671)

One product, two voltage ceilings — both are printed here

The polyolefin cover carries two different voltage figures in the manufacturer's own material. The Insulcover product page states insulation enhancement up to 400 kV. The Insulation Enhancement Products sheet, and the later revision of it, both state up to 66 kV for the same wrap-around Insulcover and reserve 765 kV for the silicone. Specify against 66 kV. That is the figure the two more recent documents agree on, it is the conservative one, and where two sources of the same manufacturer disagree the lower published number is the only defensible one to design to. If a tender demands the higher figure, get it confirmed in writing against a specific sheet revision before it goes into a schedule.

Electrical and ageing figures, side by side

PropertyPolyolefin GOCSilicone GSOCSilicone GSIOCTest method
Dielectric strength20 kV/mm (min.)>210 kV/cm10 kV/mm (min.)ASTM D149
Volume resistivity1 × 10¹³ Ω·cm (min.)1 × 10¹³ Ω·cm (min.)1 × 10¹⁰ Ω·cm (min.)ASTM D257
Ultimate elongation250% (min.)300% (min.)200% (min.)ASTM D638
Tensile after 150 °C for 168 hrsNot published3.5 N/mm² (min.)3.0 N/mm² (min.)ASTM D2671 / D638
Elongation after 150 °C for 168 hrsNot published150% (min.)100% (min.)ASTM D2671 / D638
Water absorption0.5% (max.)0.5 (max.)0.5% (max.), 24 hrs at 23 °CASTM D570
Tracking and erosionNo tracking, erosion or flame failure up to 3.25 kV for 20 minNo failure through 2.5, 2.75 and 3.0 kV for 1 hr each, then 3.25 kV for 20 minNo failure through 2.5, 2.75, 2.5 and 3.0 kV for 1 hr each, then 3.25 kV for 20 minASTM D2303
Density1.20 ± 0.2 gm/cm³Not published1.10 – 1.45 gm/cm³ASTM D792
Dielectric constant5 (max.)Not publishedNot publishedASTM D150
UV resistance, 5000 hrsNo colour changeUV and ozone resistance claimed, no figureUV resistance claimed, no figureASTM G154

"Not published" means the property does not appear on that product's sheet in the manufacturer's material — not that the material lacks the property. Dielectric strength is printed per millimetre on the polyolefin sheets and per centimetre on the GSOC sheet; both are reproduced as published.

Where the polyolefin wins

Every reason below is a published number, and every one of them is a mechanical or environmental property rather than an electrical one.

  • A harder surface. 40 ± 5 Shore D (ASTM D2240) against 65 ± 5 Shore A (ASTM D2240) on the interlocking silicone. Shore D and Shore A are different scales and a reading on the D scale is the harder material by a wide margin. On a jumper that swings against a crossarm, or a span with a tree limb resting on it, hardness is the property doing the work.
  • Higher tensile strength. 9 N/mm² minimum (ASTM D638), against 7 for GSOC and 4 for GSIOC. It is the strongest of the three as supplied.
  • Twice the roll. 30 metres per roll against 15, across every size from GOC 1 to GOC 4, so a long retrofit run carries half as many joins.
  • A published continuous temperature limit. −45 to +105 °C (IEC 216). The two silicone sheets publish ageing conditions and an installation temperature, not a continuous service range, so on a cold-climate line this is the only one of the three with a stated lower bound.
  • Weathering and dielectric figures the silicone sheets do not carry. 5000 hours of UV with no colour change (ASTM G154), a dielectric constant of 5 maximum (ASTM D150), heat shock at 90 °C for 4 hours with no cracking (ASTM D2671), and halogen-free flame retardance rated Pass (ASTM D2671).
  • Chemical exposure. The polyolefin is stated to resist corrosion from strong acid, alkali and salt — the reason it turns up on coastal and industrial-atmosphere feeders.

Where the silicone wins

Two of these are decisive on their own. The rest are margin.

  • Voltage headroom, by an order of magnitude. GSOC-EH is published to 765 kV against 66 kV for the polyolefin. Above 66 kV there is no comparison to make — the polyolefin is simply not offered there.
  • No installation tool. The Split Insulation Tube Tool has to be set up in one location and the conductor fed through it. GSOC self-locks by hand, and its sheet records installation at 0 °C without difficulty. On an energised retrofit, or anywhere the crew cannot bring a tool to the working position, this is the whole argument.
  • More elongation. 300% minimum (ASTM D638) against 250% for the polyolefin and 200% for GSIOC, which is what lets it take an irregular profile — a bundled jumper, a clamp shoulder — without a wrinkle that later holds water.
  • Wall thickness published per voltage class. 2.0 mm at 12 kV, 2.7 and 3.0 mm at 36 kV, 5.0 mm at 765 kV. You can see what the class is buying you. The GOC selection chart gives conductor size, diameter and roll length, and no wall figure at all.
  • Retained properties after ageing. After 150 °C for 168 hours (ASTM D2671) GSOC still holds 3.5 N/mm² and 150% elongation (ASTM D638). The polyolefin sheet publishes no post-ageing figure to set against it.
  • The derating statement — and its limit. The GSOC feature list states that it does not require further derating of conductors. That statement is made for GSOC and only GSOC. Neither the polyolefin sheet nor the GSIOC sheet says it, so do not carry it across, and do not let a supplier carry it across for you.
  • An optional tape layer. Self-fusing silicone tape, 63.5 mm × 0.76 mm, applies over the fitted GSOC cover for added insulation; the quantity depends on conductor size.

What this does not do

This comparison decides between three constructions from one manufacturer for one job. It does not tell you whether a cover is the right answer at all. A retrofit cover is insulation enhancement against momentary contact; it does not make an energised line safe to touch, and it is not a substitute for factory-covered conductor. That decision lives on covered conductor against a retrofit cover. The table also leaves out the Overhead Line Tube, which shares the Insulcover name but is a genuinely different polyolefin — 10 N/mm² (ASTM D638), 350% elongation (ASTM D638), 30 ± 5 Shore D (ASTM D2240) and 1 × 10¹⁴ Ω·cm (ASTM D257) — and must not be quoted as a synonym for the wrap-around GOC cover.

Send the conductor dimension, not the part number

Give the conductor size in sq.mm and its diameter in mm across the strands, the system voltage, the run length and whether the line will be dead or live during the fit. Those five facts pick the construction and the code in one reply. The covers are manufactured by Gala Thermo Shrink Pvt. Ltd., Mumbai.